I-7018
8-channel Analog Input Module |
 |
 |
 |
|
 |
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Analog Input |
Input Channels |
8 differential or 6 differential and 2 single-ended by jumper select |
Input Type |
+/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V
+/-20mA (requires optional external 125 ohm resistor)
Thermocouple Type J, K, T, E, R, S, B, N, C |
Resolution |
16-bit |
Sampling Rate |
10 Samples/ Second |
Accuracy |
+/-0.1% |
Band Width |
15.7 Hz |
Zero Drift |
0.5uV/°C |
Span Drift |
25ppm/¢XC |
Input Impedance |
20M Ohms |
Common Mode Rejection |
150dB |
Normal Mode Rejection |
100dB |
Over Voltage Protection |
+/-35V |
Open Thermocouple Detection |
No |
Photo-Isolation |
3750 Vrms |
Intra-module Isolation, Field to Logic |
3000 VDC |
Interface |
RS-485 |
Format |
N, 8, 1 (details) |
Baud Rate |
1200 ~ 115200bps |
LED Display |
1 LED as Power/ Communication indicator |
Power |
Input |
+10 to +30 Vdc |
Power Consumption |
1.0W |
Environment |
Operating temperature |
-25 to 75¢XC |
Storage temperature |
-40 to 85¢XC |
Humidity |
5 to 95% RH, non-condensing |
|
|
|
|
|
Note: We recommend to choose I-7018Z for accurate thermocouple measurement. |
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
Type |
Range¢XC
|
J |
-210 ~ +760 |
K |
-270 ~ +1372 |
T |
-270 ~ +400 |
E |
-270 ~ +1000 |
R |
0 ~ +1768 |
S |
0 ~ +1768 |
B |
0 ~ +1820 |
N |
-270 ~ 1300 |
C |
0 ~ 2320 |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
I-7018 |
8-channel Analog Input Module |
I-7018 CR |
8-channel Analog Input Module (RoHS) |
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|