Modbus Utility 1.6.8
Add power on value, safe value, WDT setting for analog/digital module.
Add CPU status readback, CPU reset events setting.
Modbus Firmware M8E16755.exe ( MBT8_167.Lib, IO_155.Lib)
Upgrade Modbus lib to v1.6.7
Upgrade I/O scan lib to v1.5.5.
Add power on value, save valaue address for analog/digital output module.
Add WDT, WDT event counts, CPU status, CPU reset events addresses.
Power on value
When the I-8000E power on, the analog/digital output modules go to their preset power on value.
Safe value
If the I-8000E looses the modbus communication for a while, the watchdog rises and all analog/digital modules go to their preset safe values. At the meanwhile, the L3 LED on the pannel flashs.
|