PROFI-5018/S
Introduction
The PROFI-5018 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 10-channel Thermocouple Input Module with High Voltage Protection. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.

Applications

- Industrial Automation
- Factory Automation
- Process Automation
- Etc…
Ordering Information
PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
---|---|---|---|
This combination include other products.
Similar Products
CPU Module | |
---|---|
CPU | 80186, 80 MHz or compatible |
EEPROM | 2 KB |
Flash | 512 KB |
SRAM | 512 KB |
Watchdog Timer | Watchdog IC CPU built-in |
LED Indicators | |
---|---|
Status | PWR LED, RUN LED, ERR LED |
Analog Input | |
---|---|
Channels | 10 channel differential thermocouple input, Isolation Voltage:2500Vrms |
Range | +/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V, +/-20mA, 0~20mA, 4~20mA (requires optional external 125 Ohms resistor), Thermocouple Type: J, K, T, E, R, S, B, N, C |
Accuracy | +/- 0.1 of FSR |
PROFIBUS | |
---|---|
Controller | Siemens SPC3 |
Transceiver | DI ADM2486 |
Baud Rate | 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M |
Isolation | 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic |
Protocol | DP-V0 |
Power | |
---|---|
Consumption | 3.5 W |
Mechanical | |
---|---|
Dimensions (mm) | 91 x 130 x 52 (W x L x H) |
Installation | DIN-Rail |
Environment | |
---|---|
Operating Temperature | -25 ~ +75℃ |
Storage Temperature | -30 ~ +80 ℃ |
Humidity | 10 ~ 90% RH, Non-condensing |
Thermocouple Type | Temperature Range °C |
---|---|
TYPE J | -210 °C ~ +1200 °C |
TYPE K | -270 °C ~ 1372 °C |
TYPE T | -270 °C ~ 400 °C |
TYPE E | -270 °C ~ 1000 °C |
TYPE R | -50 °C ~ 1765 °C |
TYPE S | -50 °C ~ 1765 °C |
TYPE B | 0 °C ~ 1820 °C |
TYPE N | -270 °C ~ 1300 °C |
TYPE C | 0 °C ~ 2320 °C |