PM-3033
Introduction
ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3033 series that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-3033 series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. Direct input from “secondary side 1A/5A” type CTs. Dedicated CTs are no longer needed, which lowers the cost of implementation. It operates over a wide input voltages range 10 ~ 500 VAC which allows worldwide compatibility. It also supports Modbus RTU, Modbus TCP or CANopen protocols for easy integration.
Applications
• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis
Ordering Information
PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
---|---|---|---|
This combination include other products.
Similar Products
AC Power Measurement | |
---|---|
Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT |
Loops | Three-phase |
Input Voltage | 10 ~ 500 V |
Input Current | 0.05 A ~ 5 A |
Input Frequency | 50/60 Hz |
W Accuracy | Better than 0.5% (PF=1; Input Current >0.5A) |
Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
Data Update Rate | 1 Second |
CT | |
---|---|
Includes CTs | 0 |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 9600, 19200 (default), 38400, 115200; DIP Switch Selectable |
Data Format | N,8,1 (default); N,8,2; E,8,1; E,8,2; O,8,1; O,8,2 |
Protocol | Modbus RTU |
Isolation | 3000 VDC |
Power | |
---|---|
Input Range | +12 ~ 48 VDC |
Consumption | 2W |
Mechanical | |
---|---|
Casing | Plastic |
Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -20 ~ +70 °C |
Storage Temperature | -25 ~ +80 °C |
Humidity | 10 ~ 90% RH, Non-condensing |