LC-101H
1-CH Lighting Control Module with AC Load Current Measurement (1 Relay output with 1 AC AI + 1 AC DI)
Introduction
LC-101H and LC-102H are lighting control modules designed specifically for smart home applications, with the former being a single-loop and the latter a dual-loop model, both equipped with AC load current measurement capabilities. These modules not only effectively control lighting circuits but also provide real-time monitoring of load current, giving users an intuitive understanding of the lighting system's operational status.
Since the lighting circuits typically use inductive loads, switching can generate strong inrush currents (approximately 10 to 20 times the working current), which may damage the relays within the modules. The LC-101H and LC-102H are equipped with high-power relays that are resistant to inrush currents, allowing them to withstand these surges, prolonging their lifespan and reducing maintenance needs.
When users turn the lights on or off, the modules can detect the relay's switching state by measuring the load current, ensuring the normal operation of the lighting control system and promptly identifying any issues. Additionally, the relays in these modules utilize a Form C design, supporting dual-loop configurations with physical switches, providing users with greater flexibility and convenience. The current measurement feature also helps users monitor load current and check the relay's switching status, ensuring that the load operates correctly in the lighting circuit and preventing relay sticking.
The LC series lighting control modules are user-friendly, allowing for installation and operation without professional skills, and can control lighting channels without the need for software. When software control is required, programming can be done via the Modbus RTU communication protocol, and the Modbus RTU communication address can be set by hardware.
Since the lighting circuits typically use inductive loads, switching can generate strong inrush currents (approximately 10 to 20 times the working current), which may damage the relays within the modules. The LC-101H and LC-102H are equipped with high-power relays that are resistant to inrush currents, allowing them to withstand these surges, prolonging their lifespan and reducing maintenance needs.
When users turn the lights on or off, the modules can detect the relay's switching state by measuring the load current, ensuring the normal operation of the lighting control system and promptly identifying any issues. Additionally, the relays in these modules utilize a Form C design, supporting dual-loop configurations with physical switches, providing users with greater flexibility and convenience. The current measurement feature also helps users monitor load current and check the relay's switching status, ensuring that the load operates correctly in the lighting circuit and preventing relay sticking.
The LC series lighting control modules are user-friendly, allowing for installation and operation without professional skills, and can control lighting channels without the need for software. When software control is required, programming can be done via the Modbus RTU communication protocol, and the Modbus RTU communication address can be set by hardware.
LC-10xH comparison table:
LC-101H | LC-102H | LC-103H | |
---|---|---|---|
Digital Input | 1 | 2 | 1 |
Relay Output | 1 | 2 | 3 |
Max. Load Current | 30 A (Resistive Load, recommend working current is 1.0 A with 220 VAC) |
16 A (Resistive Load, recommend working current is 1.5 A with 220 VAC) |
|
Max. Lighting Loads | (1) Incandescent Lamp: 6 units (2) LED(Electronic ballast): 8 units |
(1) Incandescent Lamp: 8 units (2) LED(Electronic ballast): 10 units |
|
Load Current Readback | Yes. | No | |
AC Load Current Measurement | 0 ~ 5 A | No | |
Function | Local and Remote Direct Control Relay ON/OFF and Remote Status Monitoring |
Applications

Ordering Information
PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
---|---|---|---|
This combination include other products.
Similar Products
Software | |
---|---|
Function | Local and Remote Direct Control Relay ON/OFF and Remote Status Monitoring |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
Surge (IEC 61000-4-5) | ±2 kV for Power |
LED Indicators | |
---|---|
Status | 1 LED as Power Indicator |
Digital Input | |
---|---|
Channels | 1 |
Type | Wet Contact, 90 ~ 240 VAC |
ON Voltage Level | 65 VAC |
OFF Voltage Level | 56 VAC |
Isolation | 3000 VDC |
Input Impedance | 68 KΩ, 2W |
Relay Output | |
---|---|
Channels | 1 |
Type | Power Relay, Form C (SPDT N.O+N.C..) |
Contact Rating | 30 A @ 250 VAC |
AC Load Current Measurement | Yes, 0 ~ 5 A range with 3% of FSR Accuracy. |
Operate Time | 15 ms Max |
Release Time | 22 ms Max. |
Electrical Endurance | 100,000 ops. |
Mechanical Endurance | 10,000,000 ops |
Power on Value | Yes |
Safe Value | Yes |
Application Specification | (1).Incandescent Lamp: 40W/ 220VAC * 5 Sets (2).LED(Electronic ballast): 40W/ 220VAC *8 Sets |
Ethernet | |
---|---|
Node Address | 32 to 63 for hardware configuration |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | Hardware Configuration: Fixed 9600 bps Software Configuration: 1200 to 115200 bps |
Data Format | N,8,1/O,8,1/E,8,1/N,8,2 |
Protocol | Modbus RTU/DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | 10 ~ 30 VDC |
Consumption | 1.9 W Max. |
Mechanical | |
---|---|
Dimensions (mm) | 72 mm x 95 mm x 57 mm |
Installation | DIN-Rail |
Environment | |
---|---|
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -30 ~ +75°C |
Humidity | 10 ~ 95% RH, Non-condensing |