I-7590
Introduction
The I-7590 is specially designed for M-Bus slave device. It is a serial bus to M-Bus convertor. First, for serial bus, it offers RS-232, RS-422 and RS-485 three kinds of communication way. Second, the I-7590 has two rotary switches, one for serial port baud and the other for M-Bus port baud. Third, the I-7590 uses transparent transmission between serial bus and M-Bus communication. Through these three designs, it is easy to communicate with any standard M-Bus slave.

Applications
The M-Bus (Meter‐Bus) is a bus optimized for the reading of measurement instruments like: energy counters, hot and cold water counters, gas, pressure, sensors and actuators, etc….

Ordering Information
PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
---|---|---|---|
This combination include other products.
Similar Products
COM Ports | |
---|---|
Ports | 1 x RS-232/485/422, Non-isolated |
Baud Rate | 300 ~ 115200 bps |
Parity | None, Even, Odd, Mark, Space |
Data Bit | 5, 6, 7, 8 |
Stop Bit | 1, 2 |
M-Bus | |
---|---|
Ports | 1 |
Baud Rate | 300 ~ 2400 bps and user-defined baud rate |
Data Bit | 5, 6, 7, 8 |
Stop Bit | 1, 2 |
Parity | None, Even, Odd, Space, Mark |
Isolation | 3750 Vrms for photo-couple |
Current Protection | short-circuit protection |
Power | |
---|---|
Consumption | 1.8 W @ 24 VDC (with 1 slave device), 11.8 W @ 24 VDC (with 100 slave devices) |
Mechanical | |
---|---|
Dimensions (mm) | 72 x 120 x 36 (W x H x D) |
Installation | DIN-Rail |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 ℃ |
Storage Temperature | -30 ~ +80 ℃ |
Humidity | 10 ~ 90% RH, Non-condensing |
- Provide M-Bus user-defined baud rate
- Provide serial bus user-defined baud rate
- Check firmware version
- Update firmware


Baud Rate Selection by Rotary Switch
|
||||||
Switch Value | 0 | 1 | 2 | 3 | 4 | 5 |
Baud [bps] | 300 | 600 | 1200 | 2400 | 4800 | 9600 |
Switch Value | 6 | 7 | 8 | 9 | A ~ F | |
Baud [bps] | 19200 | 38400 | 57600 | 115200 | User-defined | |
The data format of serial bus baud rate of switch value 0 ~ 9 is 8, n, 1. The data format of M-Bus bus baud rate of switch value 0 ~ 9 is 8, e, 1. |
Execution Mode by DIP Switch
|
||
DIP 1 (Init) | DIP 2 (Mode) | Description |
---|---|---|
OFF | OFF | Run Firmware |
OFF | ON | Configure |
ON | OFF | Update Firmware |
Support Meter
The following meters have been tested with the I-7590 communication: |
|||
Manufacture | Picture | Model Type | Meter Type |
---|---|---|---|
Danfoss | ![]() |
SONOMETER 500 | Heat Meter |
SENSUS | ![]() |
405S | Water Meter |
WESER | ![]() |
PUL | Heat Meter |
DIEHL | ![]() |
ALTAIR V4 | Water Meter |
Wason | ![]() |
LXZD-Y3 | Water Meter |