I-7188E/8000E Hardware 003

back

Q : How many PCs can be connected to one 7188E/8000E device?

¡@

Ans : It depends on how many serial ports on the 7188E/8000E and how many serial ports of 7188E/800E that each PC connected on it.

7188E/8000E has 32 sockets totally and it reserves some sockets for listening.

7188E/8000E provides one command port for configuring all data (serial) ports. Thus, no matter how many data (serial) ports of 7188E/8000E you used, you need one more socket connection for the command port to configure them.

 

CMD
Ports
Data
Ports
Listening Sockets
=1 CMD + all Data
Left Sockets
=Max. - Listening
PCs with all ports
=Left / (1 CMD + all Data)
PCs with 1 port
=Left / (1 CMD+1 Data)
7188E1 1 1 2 32 - 2 = 30 30 / 2 = 15 30 / 2 = 15
7188E2
7188EA/X
1 2 3 32 - 3 = 29 29 / 3 = 9 29 / 2 = 14
7188E3 1 3 4 32 - 4 = 28 28 / 4 = 7 28 / 2 = 14
7188E4 1 4 5 32 - 5 = 27 27 / 5 = 5 27 / 2 = 13
7188E5 1 5 6 32 - 6 = 26 26 / 6 = 4 26 / 2 = 13
7188E8 1 8 9 32 - 9 = 23 23 / 9 = 2 23 / 2 = 11
8430/8830
8431/8831
1 2 3 32 - 3 = 29 29 / 3 = 9 29 / 2 = 14

Note:

  1. CMD port = Command port (TCP port 10000)

    It's used to configure all data ports (TCP port 10001 ~ 10008) of a 7188E/8000E, such as baudrate, data format ... etc.

  2. Data port (TCP port 10001 ~ 10008 whichs are mapped to serial port 1 ~ 8 of 7188E/8000E), it's used to send/receive data only.

  3. Listening Sockets (of 7188E/8000E) = Number of Data ports + 1 CMD port
    (VCOM3010.exe reserves 2 more sockets for TELNET and UDP CMD port listening.)

  4. Left Sockets (of 7188E/8000E) = Max. (32) sockets - Listening sockets

  5. Number of PCs could be connected to one 7188E/8000E with all data ports used
    = Left sockets / [Number of Data ports + 1 CMD port ]

  6. Number of PCs could be connected to one 7188E/8000E with 1 data port used
    = Left sockets / ( 1 Data port + 1 Command port ) = Left sockets / 2

back

Written by Gary Lin 

Date:2002/12/16